DatasheetsPDF.com

NJB1-X1

CHiNT

Protection Relay

NJB1-X1 Relay (Phase Sequence, Phase Failure Protection) 1. General NJB1-X1 relay (phase sequence, phase failure protect...


CHiNT

NJB1-X1

File Download Download NJB1-X1 Datasheet


Description
NJB1-X1 Relay (Phase Sequence, Phase Failure Protection) 1. General NJB1-X1 relay (phase sequence, phase failure protection) is used as an phase sequence and phase failure protection device in control circuits with an AC voltage of 200V~500V and a frequency of 50Hz to make and break the circuit. It cannot monitor the phase failure of motor load. The products meet the requirement of standard IEC 60947-5-1 2. Type designation N JB 1 - X1 Function code: X1: phase sequence, phase failure relay Design sequence No. Protection and monitoring relay Company code Relay Protection Relay 3. Operation conditions 3.1 Rated operational voltage: AC 200V~500V 3.2 Operation time: phase sequence, phase failure ≤ 0.1s 3.3 Contact capacity: Ue/Ie: AC-15 220V/0.75A, 380V/0.47A; Ith: 3A 3.4 Mounting type: rail type, installation type 3.5 Power consumption: ≤3VA 3.6 Note: In normal operation, the N/O contact of the relay is closed, the operation indicator is on. 4. Wiring diagram L1 L2 L3 Load Input Powersupply shareswith theratedinput voltage L1 L2 L3 18 Output 15 16 5. Overall and mounting dimensions (mm) 114max L1 L2 L3 R NJB1-X1 15 18 16 102±0.50 102max 22.5max I-03 > >> ...




Similar Datasheet