Current Transducer HAS 50 ... 600-P For the electronic measurement of currents: DC, AC, pulsed..., with galvanic separation between the primary circuit and the secondary circuit. IP N = 50 ... 600 A Electrical data Type Primary nominal Primary current, RoHS since RMS current measuring range date code IP N (A) HAS 50-P 50 IP M (A) ±150 46065 HAS 100-P 100 ±300 46062 HAS 200-P 200 ±600 76273 HAS 300-P 300 ±900 76273 HAS 400-P 400 ±900 46131 HAS 500-P 500 ±900 46216 HAS 600-P 600 ±900 76273 UC Supply voltage (±5 %) 1) ±15 V IC Current consumption ±15 mA RINS Insulation resistance @ 500 V DC > 1000 MΩ Uout Output voltage (Analog) @ ±IP N, RL = 10 kΩ, TA = 25 °C ±4 V Rout Output internal resistance approx 100 Ω RL Load resistance 10 kΩ Accuracy - Dynamic performance data Features ● Hall effect measuring principle ● Insulating plastic case made of polycarbonate PBT recognized according to UL 94-V0. Advantages ● Easy mounting ● Low power consumption ● Small size and space saving ● Only one design for wide current ratings range ● High immunity to external interference. εtot Total error @ IP N, TA = 25 °C (excluding offset) < ±1 % of IP N εL Linearity error 2) (0 ... ±IP N) < ±1 % of IP N UO E Electrical offset voltage, TA = 25 °C < ±20 mV UO H Hysteresis offset voltage @ IP = 0, after an excursion of 1 × IP N < ±20 mV TCUO E Temperature coefficient of UO E HAS 50-P ...