Current Transducer
Current Transducer HAS 50 ... 600-S
For the electronic measurement of currents: DC, AC, pulsed..., with galvanic separat...
Description
Current Transducer HAS 50 ... 600-S
For the electronic measurement of currents: DC, AC, pulsed..., with galvanic separation between the primary circuit and the secondary circuit.
IP N = 50 ... 600 A
Electrical data
Type
Primary nominal Primary current, RoHS since
RMS current measuring range 1) date code
IP N (A)
HAS 50-S
50
IP M (A) ±150
45217
HAS 300-S
300
±900
45326
HAS 400-S
400
±900
45333
HAS 500-S
500
±900
45201
HAS 600-S
600
±90d0Cl
4d5Cp260
UC
Supply voltage (±5 %) 1)
±15
V
IC
Current consumption
±15
mA
RINS Insulation resistance @ 500 V DC
>1000
MΩ
Uout Output voltage (Analog) @ ±IP N, RL = 10 kΩ, TA = 25 °C ±4
V
Rout RL
Output internal resistance
approx
Load resistance 2)
IP
100
Ω
>1 UC
kΩ
RM
Accuracy - Dynamic performance data
UC
ε
Error @ IP N, TA = 25 °C (excluding offset)
<±1 % of IP N
εL
Linearity error 3) (0 ... ±IP N)
<±1 % of IP N
UO E Electrical offset voltage, TA = 25 °C
<±20
mV
UO H Hysteresis offset voltage @ IP = 0,
after an excursion of 1 × IP N <±20
mV
TCUO E Temperature coefficient of UO E HAS 50-S
<±2
mV/K
HAS 300 ... 600-S <±1
mV/K
TCUout Temperature coefficient of Uout (% of reading) tD 90 Delay time to 90 % of IP N 4) BW Frequency bandwidth (−3 dB) 5)
<±0.1
%/K
<3
µs
DC ... 50
kHz
General data
TA
Ambient operating temperature
TS
Ambient storage temperature
m
Mass
approx
Standards
−10 ....