Current Transducer
Current Transducer HAS 50 ... 600-P
For the electronic measurement of currents: DC, AC, pulsed..., with galvanic separat...
Description
Current Transducer HAS 50 ... 600-P
For the electronic measurement of currents: DC, AC, pulsed..., with galvanic separation between the primary circuit and the secondary circuit.
IP N = 50 ... 600 A
Electrical data
Type
Primary nominal Primary current, RoHS since
RMS current measuring range date code
IP N (A)
HAS 50-P
50
IP M (A) ±150
46065
HAS 100-P
100
±300
46062
HAS 200-P
200
±600
76273
HAS 300-P
300
±900
76273
HAS 400-P
400
±900
46131
HAS 500-P
500
±900
46216
HAS 600-P
600
±900
76273
UC
Supply voltage (±5 %) 1)
±15
V
IC
Current consumption
±15
mA
RINS Insulation resistance @ 500 V DC
> 1000
MΩ
Uout Output voltage (Analog) @ ±IP N, RL = 10 kΩ, TA = 25 °C ±4
V
Rout Output internal resistance
approx
100
Ω
RL
Load resistance
10
kΩ
Accuracy - Dynamic performance data
Features
● Hall effect measuring principle ● Insulating plastic case made of
polycarbonate PBT recognized according to UL 94-V0.
Advantages
● Easy mounting ● Low power consumption ● Small size and space saving ● Only one design for wide current
ratings range ● High immunity to external
interference.
εtot
Total error @ IP N, TA = 25 °C (excluding offset)
< ±1 % of IP N
εL
Linearity error 2) (0 ... ±IP N)
< ±1 % of IP N
UO E Electrical offset voltage, TA = 25 °C
< ±20
mV
UO H Hysteresis offset voltage @ IP = 0,
after an excursion of 1 × IP N < ±20
mV
TCUO E Temperature coefficient of UO E HAS 50-P
...