Document
LC-X1265
For standby power supplies Expected trickle life:Approx.6 years at 25℃,approx.10 years at 20℃
■Dimensions(mm)
Terminal type
18 18 M6
Contents indicated (including the recycle marking, etc) are subject to change without notice.
Battery case resin:standard(UL94HB)
■Specification
Nominal Voltage Rated Capacity(20HR) Length Width Dimensions Height Total height Approx. Mass Terminal 12V 65Ah 350 mm 166 mm 175 mm 175 mm 19.5 kg M6 threaded post Bolt and Nut type
■Duration of discharge vs. discharge current
30 20 10 (hour) 40℃ 25℃
Duration of discharge
5 3
■Characteristics
Capacity (25 ℃) 20 hour rate 10 hour rate 5 hour rate 1 hour rate
Fully charged battery
60 30 0℃ -15℃
(minute)
65Ah 59Ah 53Ah 40Ah 7 mΩ 102% 100% 85% 65% 91% 82% 64%
Internal Resistance Temperature Dependency of Capacity (20 hour rate) Self Discharge (25 ℃)
10 5 3
(25 ℃) 40 ℃ 25 ℃ 0℃ -15 ℃ After 3 months After 6 months After 12 months
1
1
3
10
30
100
300
1000
Discharge current(A)
■Watt Table(25℃)
Cut-off V
(Wattage/Battery)
15min 1127 1116 1093 1017 949 20min 956 951 935 888 865 30min 742 734 725 709 685 45min 533 520 515 507 499 1h 501 494 484 474 465 1.5h 321 313 307 300 292 2h 290 289 281 272 259 3h 201 198 196 193 189 4h 158 157 156 154 152 5h 131 127 126 125 122 6h 115 115 114 113 111 10h 70.8 70.8 70.1 69.7 69.0 20h 39.0 39.0 38.9 38.8 38.6 24h 32.4 32.4 32.3 32.2 32.0
3min 2235 2180 2010 1787 1509
5min 1884 1851 1735 1554 1374
10min 1439 1422 1386 1284 1145
9.6V 9.9V 10.2V 10.5V 10.8V
■Ampere Table(25℃)
Cut-off V
(Ampere/Battery)
20min 82.4 82.0 80.6 76.6 74.5 30min 63.4 62.7 62.0 60.6 58.5 45min 45.4 44.3 43.9 43.2 42.5 1h 42.5 41.9 41.1 40.3 39.4 1.5h 27.2 26.5 26.0 25.4 24.7 2h 24.5 24.4 23.8 22.9 21.9 3h 16.9 16.6 16.4 16.2 15.8 4h 13.2 13.1 13.0 12.9 12.8 5h 10.9 10.6 10.5 10.4 10.2 6h 9.60 9.60 9.52 9.41 9.26 10h 5.90 5.90 5.84 5.81 5.75 20h 3.25 3.25 3.24 3.23 3.21 24h 2.70 2.70 2.69 2.68 2.66
3min 201 196 181 161 136
5min 169 166 156 139 123
10min 129 127 124 115 102
15min 98.0 97.0 95.0 88.4 82.5
9.6V 9.9V 10.2V 10.5V 10.8V
2008.10
http://www.Datasheet4U.com
■Charging Method
Trickle use
(25℃)
■Cut off voltage
Discharge current 3.25A- 13A- 32.5A- 65A- 130A13A 32.5A 65A 130A 195A 10.5 10.2 9.9 9.3 8.7
Control voltage 13.6-13.8V;Initial current 9.75A or smaller Cut off voltage(V)
■Influence of Temperature on Trickle life
100
■Residual capacity test result
120 Capacity Retention Ratio(%) 100 80 60 40 20 0 40℃ (104℉) 30℃ (86℉) 25℃ (77℉) 5℃ (41℉)
Service Life (Years)
10
①Charging Voltage 2.275V/Cell
1
0.1 0 10 203 04 0 506 0
0
2
4
6
8
101
21
4
161
8
20
Temperature (℃)
Storage Period (Month)
■Constant-voltage and constant-current charge characteristics ■Discharge capacity by temperature and by discharge current
160 0.3 Charge Quantity (%) Charge Current (CA) 140 120 100 80 60 40 20 0 0 0 4 8 12 16 20 Charge Time (H)
Battery Voltage Charge Quantity (to-Discharge Quantity
①Discharge 100%(0.05CA*20H) 50%(.