Valve-Regulated Lead Acid Batteries
VALVE-REGULATED LEAD ACID BATTERIES: INDIVIDUAL DATA SHEET
LC-X1265P
For standby power supplies. Expected trickle life...
Description
VALVE-REGULATED LEAD ACID BATTERIES: INDIVIDUAL DATA SHEET
LC-X1265P
For standby power supplies. Expected trickle life: Approx. 6 years at 25°C, Approx. 10 years at 20°C.
Dimensions (mm)
Terminal type: M6 bolt and nut
13.799±0.79 (350±2) 10.43 (265) 5.43 (137.8) 0.28 (7)
0.71 (18)
6.535±0.079 (166±2) 2.5 (63.5) 1.9 0.71 (18) (48.2 )
6.889±0.079 (175±2)
3.14 (79.8)
Photo/Label for reference only.
13.53 (343.6) 6.48 (164.5)
Specifications
Nominal Voltage Rated Capacity (20 hour rate) Length Dimensions Width Height Total Height Approx. mass
Standard Terminals and Resin
12V 65Ah 13.780 inches (350 mm) 6.535 inches (166 mm) 6.890 inches (175 mm) 6.890 inches (175 mm) 44.1 lbs. (20.0 kg) LC-X1265P LC-P1265P
Battery case resin: Standard (UL94HB) Color is black. Optional (UL94V-0) Color is grey .
6.1 (155)
Discharge characteristics 77°F (25°C)
13.5 13.0 12.5 12.0 11.5 11.0 10.5 10.0 9.5 9.0 8.5 8.0
0 1 2 4 6 8 10 20 40 60 2
(Note)
UL94HB M6 Bolt and Nut UL94V-0 M6 Bolt and Nut
Terminal voltage (V)
16.25A
3.25A
♦ Please contact Panasonic for availability on optional items. Optional items may be subject to minimum order quantities.
4
6 8 10
20
40
(Minute)
(Hour)
Duration of discharge
Characteristics
Capacity (note) 77˚F (25˚C) 20 hour rate (3.25A) 10 hour rate (5.9A) 5 hour rate (10.6A) 1 hour rate (40A) 1.5 hour rate discharge Cut-off voltage 10.5 V Fully charged battery 77˚F (25˚C) 104˚F (40˚C) 77˚F (25˚C) 32˚F (0˚C) 5˚F (-15˚C) Residual capacity after st...