DIESEL ENGINE-GENERATOR SET
A tognum Group Brand
Diesel Engine-Generator sET 500-XC6DT2
500 ekW / 60 Hz / Standby 208 - 4160V
System Ratings
Stan...
Description
A tognum Group Brand
Diesel Engine-Generator sET 500-XC6DT2
500 ekW / 60 Hz / Standby 208 - 4160V
System Ratings
Standby
OE Type Phase PF Hz kW kVA AMPS skVA@30% Voltage Dip Generator Model* Temp Rise Connection 208V** 3 0.8 60 500 625 1735 1470 572RSL4029 130°C/27°C 12 LEAD LOW WYE 240V** 3 0.8 60 500 625 1504 1470 572RSL4029 130°C/27°C 12 LEAD HI DELTA 480V** 3 0.8 60 500 625 752 1280 572RSL4027 130°C/27°C 12 LEAD HI WYE 600V** 3 0.8 60 500 625 601 1040 572RSS4270 125°C/40°C 4 LEAD WYE 4160V 3 0.8 60 500 625 87 1240 573FSM4354 130°C/27°C 6 LEAD WYE
Note: Prime Power is not available for this model. * The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration. ** UL2200 Offered
Facts
EPA Tier 2 Certified Engine-Generator Set Tested to ISO 8528-5 for Transient Response // UL2200, CSA Listing Offered // Accepts Rated Load in One Step Per NFPA 110, Level 1 // All engine-generator sets are prototype and factory tested // MTU Onsite Energy is a single source supplier // Global Product Support www.DataSheet4U.com // 2 Year Standard Warranty // Series 60 (6063HK36) Diesel Engine - 14.0 Liter Displacement - Electronic Unit Pump Injection - 4-Cycle
// // // //
//
//
Complete Range of Accessories Permanent Magnet Generator (PMG) - Brushless, Rotating Field - 300% Short Circuit Capability...