Document
A tognum Group Brand
DIESEL ENGINE-GENERATOR SET 2000-XC6DT2 2000 ekW 60 Hz Standby
/ / 1860 ekW / 60 Hz / Prime
480 - 13.8kV
System Ratings
Standby
Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30% Voltage Dip Generator Model* Temp Rise Connection 480V** 3 0.8 60 2000 2500 3007 5800 744RSL4054 130°C/27°C 4 BAR WYE 600V 3 0.8 60 2000 2500 2406 3600 744RSS4292 125°C/40°C 4 BAR WYE 4160V 3 0.8 60 2000 2500 347 5100 744FSM4374 130°C/27°C 4 BAR WYE 12470V 3 0.8 60 2000 2500 116 C/F 1020FDH5582 130°C/27°C 4 BAR WYE 13200V 3 0.8 60 2000 2500 109 C/F 1020FDH5582 130°C/27°C 4 BAR WYE 13800V 3 0.8 60 2000 2500 105 C/F 1020FDH5582 130°C/27°C 4 BAR WYE
Prime
Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30% Voltage Dip Generator Model* www.DataSheet4U.com Temp Rise Connection 480V 3 0.8 60 1860 2325 2797 5800 744RSL4054 105°C/40°C 4 BAR WYE 600V 3 0.8 60 1860 2325 2237 3600 744RSS4292 105°C/40°C 4 BAR WYE 4160V 3 0.8 60 1860 2325 323 5100 744FSM4374 105°C/40°C 4 BAR WYE 12470V 3 0.8 60 1860 2325 108 C/F 1020FDH5582 105°C/40°C 4 BAR WYE 13200V 3 0.8 60 1860 2325 102 C/F 1020FDH5582 105°C/40°C 4 BAR WYE 13800V 3 0.8 60 1860 2325 97 C/F 1020FDH5582 105°C/40°C 4 BAR WYE
* The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration. ** UL2200 Offered
2
// / /
2000-XC6DT2
Facts
// // // // // // // // // //
EPA Tier 2 Certified Engine-Generator Set Tested to ISO 8528-5 for Transient Response UL2200, CSA Listing Offered Accepts Rated Load in One Step Per NFPA 110, Level 1 All engine-generator sets are prototype and factory tested MTU Onsite Energy is a single source supplier Global Product Support 2 Year Standard Warranty Custom Design for Any Application 16V4000 G43 Diesel Engine - 76.3 Liter Displacement - Common Rail Injection - 4-Cycle
// //
//
//
Complete Range of Accessories Permanent Magnet Generator (PMG) - Brushless, Rotating Field - 300% Short Circuit Capability - 2/3 Pitch Windings Digital Control Panel(s) - UL Recognized, , NFPA 110 - Complete System Metering - LCD Display Cooling System - Integral Set-Mounted - Engine Driven Fan
STANDARD EQUIPMENT
//
Engine
Brushless Alternator with Brushless Pilot Exciter 4 Pole, Rotating Field 130°C Standby Temperature Rise 1 Bearing, Sealed Flexible Coupling Full Amortisseur Windings 125% Rotor Balancing 3-Phase Voltage Sensing ±.25% Voltage Regulation 100% of Rated Load - One Step 3% Maximum Harmonic Content
Air Cleaner Oil Pump Full Flow Oil Filter Jacket Water Pump Inter Cooler Water Pump Thermostats Exhaust Manifold – Dry Blower Fan & Fan Drive Radiator - Unit Mounted Electric Starting Motor - 24V Governor – Electric Isochronous Base - Structural Steel SAE Flywheel & Bell Housing Charging Alternator - 24V Battery Box & Cables Flexible Fuel Connectors Flexible Exhaust Connection EPA Certified Engine
//
Digital Control Panel(s)
//
Generator
NEMA MG1, IEEE and ANSI standards compliance for temperature rise and motor starting www.DataSheet4U.com Sustained short circuit current of up to 300% of the rated current for up to 10 seconds Self-Ventilated and Drip-Proof Superior Voltage Waveform Digital, Solid State, Volts-per-Hertz Regulator No Load to Full Load Regulation
Digital Metering Engine Parameters Generator Protection Functions Engine Protection SAE J1939 Engine ECU Communications Windows-Based Software Multilingual Capability Remote Communications to our RDP-110 Remote Annunciator 16 Programmable Contact Inputs 7 Contact Outputs UL Recognized, , CE Approved Event Recording IP 54 Front Panel Rating with Integrated Gasket NFPA110 Level Compatible
3
// / /
2000-XC6DT2
Application data
//
Engine
MTU Detroit Diesel 16V4000 G43 (T1638A36) 4-Cycle 16-V 4,656 (76.3) 6.69 (17) 8.27 (21) 16.5:1 1,800 ADEC 3,058 (2,280) 2,709 (2,020) ±.25% 60 Hz Dry
//
Fuel Consumption
STANDBY 147.3 (558) 112.6 (426) 78.9 (299) PRIME 128.6 (487) 100.7 (381) 69.9 (265)
Manufacturer Model Type Arrangement Displacement: Cu In (lit) Bore: in (cm) Stroke: in (cm) Compression Ratio Rated RPM Engine Governor Max Power: Standby: bhp (kWm) Max Power: Prime: bhp (kWm) Regulation Frequency Air Cleaner
At 100% of Power Rating: gal/hr (lit/hr) At 75% of Power Rating: gal/hr( lit/hr) At 50% of Power Rating: gal/hr (lit/hr)
//
Cooling - Radiator System
PRIME 104 (40) 0.5 (0.12) 357 (1,350) 154 (583) 43,790 (770) 32,530 (572) 9,871 (173.6)
//
Liquid Capacity (Lubrication)
79.3 (300) 46.2 (175) 13.2 (50) 172 (651)
STANDBY Ambient Capacity of Radiator: °F (°C) 104 (40) Max. Restriction of Cooling Air, Intake, and Discharge Side of Rad.: in. H20 (kPa) 0.5 (0.12) Water Pump Capacity: gpm (lit/min) 357 (1,350) After Cooler Pump Capacity: gpm (lit/min) 154 (583) Heat R.