Document
Embedded Power for Business-Critical Continuity
BXB100 Series
Single output
Total Power: Input Voltage: # of Outputs:
Rev.10.16.08_121 BXB100 Series of 3
66 - 100 W 18 - 36 V 36 - 75 V Single
Electrical Specifications
Input
Special Features
• • • Industry standard footprint High power density (36.5 W/in3) MTBF >1.4 million hours (Bellcore 332) • Input voltage to ETS300-132-2 • Adjustable output voltage • No minimum load required • Separate case ground pin • Undervoltage lockout (UVLO) • UL, VDE and CSA safety approvals • 2 year warranty
Input voltage range: Input current: Input current (max.): (See note 4) Input reflected ripple: Active low remote ON/OFF: Logic compatiblity: ON: OFF: Undervoltage lockout:
24 Vin nominal 48 Vin nominal No load Remote OFF 48 V models (See note 6)
18 - 36 Vdc 36 - 75 Vdc 100 mA max. 20 mA max. 4 A max. @ lo max. and Vin = 0 to 75 V 5 mA pk-pk
Start-up time: (see note 8)
(See note 7) Open collector ref to -input 1.2 Vdc max. Open circuit 24 Vin: power-up 17 V 24 Vin: power-down 16 V 48 Vin: power-up 34 V 48 Vin: power-down 32.5 V Power up 20 ms Remote ON/OFF 20 ms Low line to high line Full load to min. load At turn on and turn-off 3.3 V and 5 V 12V and 15 V 60% to 110% ±1.0% ±0.05% ±0.10% 0% None None 75 mV pk-pk, 20 mV rms 100 mV pk-pk, 30 mV rms
Output
Voltage adjustability: Setpoint accuracy: Line regulation: Load regulation: Minimum load: Overshoot:
Safety
VDE0805/EN60950/IEC950 UL1950 CSA C22.2 No. 950
Undershoot: Ripple and noise: 5 Hz - 20 MHz (see note 1)
Embedded Power for Business-Critical Continuity
Output Continued
Ripple and noise: 5 Hz - 20 MHz (see note 1) Temperature coefficient: Transient response: (see note 2) Remote Sense: 3.3 V and 5 V 12V and 15 V 75 mV pk-pk, 20 mV rms 100 mV pk-pk, 30 mV rms ±0.01% / ºC
Rev.10.16.08_121 BXB100 Series of 3
±2.0% max. deviation 170 µs recovery to within ±1.0% 0.5 Vds transmission line drop compensation
EMC Charateristics
Conducted emissions: (see note 3) EN55022 (See note 3) FCC part 15 EN55022, CISPR22 Level A Level A Level A
General Specifications
Efficiency: Isolation voltage: Input/case Input/output Output/case Fixed Bellcore 332 MIL-HDBK-217F @ 40 °C, 100% load See table 1500 Vdc 1500 Vdc 1500 Vdc 500 kHz typ. VDE0805, EN60950, IEC950 UL1950, CSA C22.2 No. 950 Aluminum baseplate with plastic case UL94V-0 110 g (3.88 oz) 1,400,000 hours 580,000 hours min.
Switching frequency: Approvals and standards: (see note 5) Case material: Material flammability: Weight: MTBF:
Protection
Short-circuit: Overvoltage: Undervoltage: Thermal: Continuous, automatic recovery Non-latching Non-latching 110 °C baseplate, automatic recovery
Telecom Specifications
Central office interface A: ETS300-132-2
Environmental Specifications
Thermal performance: Altitude: Vibration: Operating case temp. Non-operating Operating Non-operating 5 - 500 Hz -40 ºC to +100 ºC -55 ºC to +125 ºC 10,000 feet max. 40,000 feet max. 2.4 G rms (approx.)
Embedded Power for Business-Critical Continuity
Americas Ordering Information
Output Power (Max.) Input Voltage OVP Output Voltage Output Current (Min.) Output Current (Max.) Efficiency (Typ.) Regulation Line Load Model Number
100 W 100 W 100 W
18 - 36 Vdc 36 - 75 Vdc 36 - 75 Vdc
14.5 Vdc 6.5 Vdc 14.5 Vdc
12 V 5V 12 V
0A 0A 0A
8.33 A 20 A 8.33 A
85% 83% 86%
±0.05% ±0.05% ±0.05%
±0.1% ±0.1% ±0.1%
BXB100-24S12FLTJ BXB100-48S05FLTJ BXB100-48S12FLTJ
5810 Van Allen Way Carlsbad, CA 92008 USA Telephone: +1 760 930 4600 Facsimile: +1 760 930 0698
Rev.10.16.08_121 BXB100 Series 3 of 3
Europe (UK)
External Output Trimming Output can be externally trimmed by using the method shown.
8 8
Notes
1 Measured with 10 µF tantalum capacitor and 1 µF ceramic capacitor across output. 2 di/dt = 0.1 A/1 µs, Vin = 48 Vdc, Tc = 25 °C, load change = 0.5 lo max. to 0.75 lo max. and 0.75 Io max. to 0.5 Io max. 3 Units should be characterised within systems. External components required. 4 Input fusing is recommended based on surge current and maximum input current. 5 This product is only for inclusion by professional installers within other equipment and must not be operated as a stand alone product. 6 Simulated source impedance of 12 µH. 12 µH inductor in series with +Vin. 7 Active high remote on/off option is available (standard product is active low), designate with the suffix ‘FHT’ e.g. BXB100-48S05FHTJ. Consult factory for further details and options. 8 Start-up into resistive load. 9 “J” suffix designation for RoHS 6/6.
Waterfront Business Park Merry Hill, Dudley W.