2-Electrode-Arrester
Surge Arrester 2-Electrode-Arrester
A71-H35X Ordering code: B88069X2200xxxx a)
DC spark-over voltage 1) 2) Impulse spa...
Description
Surge Arrester 2-Electrode-Arrester
A71-H35X Ordering code: B88069X2200xxxx a)
DC spark-over voltage 1) 2) Impulse spark-over voltage at 100 V/µs - for 99 % of measured values - typical values of distribution
www.DataSheet4U.com
3500 ± 20 < 4900 < 4800 < 5000 < 4900 2.5 2.5 2.5 2.5 > 10 <1 ~ 20 ~1 ~ 180 ~ 1.5 -40 ... +90 40/ 90/ 21 3500 YY O
3500 YY O - Nominal voltage - Year of production - Non radioactive
V % V V V V kA kA A A GΩ pF V A V g °C
at 1 kV/µs
- for 99 % of measured values - typical values of distribution
Nominal impulse discharge current (wave 8/20 µs) Single impulse discharge current (wave 8/20 µs) Nominal alternating discharge current (50 Hz, 1 s) Alternating discharge current (50 Hz, 9 cycles) Insulation resistance at 100 Vdc Capacitance at 1 MHz Arc voltage at 1 A Glow to arc transition current Glow voltage Weight Operation and storage temperature Climatic category (IEC 60068-1) Marking, green
a)
xxxx = S102 (100 pcs on 5 taped stripes) = T502 (500 pcs on tape and reel)
1) 2)
At delivery AQL 0.65 level II, DIN ISO 2859 In ionized mode Terms in accordance with ITU-T Rec. K.12 and DIN 57845/VDE0845
AB E / AB PM Page 1 of 2
Issue 05, 27.10.2003
Surge Arrester 2-Electrode-Arrester
A71-H35X Ordering code: B88069X2200xxxx a)
www.DataSheet4U.com
Not to scale Dimensions in mm Non controlled document