2-Electrode-Arrester
Surge Arrester 2-Electrode-Arrester
A80-A350X Ordering code: B88069X2230xxxx a)
DC spark-over voltage 1) 2) Impulse sp...
Description
Surge Arrester 2-Electrode-Arrester
A80-A350X Ordering code: B88069X2230xxxx a)
DC spark-over voltage 1) 2) Impulse spark-over voltage at 100 V/µs - for 99 % of measured values - typical values of distribution at 1 kV/µs - for 99 % of measured values - typical values of distribution
350 ± 20 < 700 < 650 < 900 < 800 20 25 20 100 > 10 < 1.5 ~ 15 ~ 0.5 ~ 60 ~ 1.5 -40 ... +90 40/ 90/ 21 350 YY O
350 YY O - Nominal voltage - Year of production - Non radioactive
V % V V V V kA kA A A GΩ pF V A V g °C
Nominal impulse discharge current (wave 8/20 µs) Single impulse discharge current (wave 8/20 µs) Nominal alternating discharge current (50 Hz, 1 s) Alternating discharge current (50 Hz, 9 cycles) Insulation resistance at 100 Vdc Capacitance at 1 MHz Arc voltage at 1 A Glow to arc transition current Glow voltage Weight Operation and storage temperature Climatic category (IEC 60068-1) Marking, blue
a)
xxxx = C102 (container with 100 pcs.) = C103 (container with 1000 pcs.)
1) 2)
At delivery AQL 0.65 level II, DIN ISO 2859 In ionized mode Terms in accordance with ITU-T Rec. K.12 and DIN 57845/VDE0845
AB E / AB PM Page 1 of 2
Issue 04, 01.09.2003
Surge Arrester 2-Electrode-Arrester
A80-A350X Ordering code: B88069X2230xxxx a)
Not to scale Dimensions in mm Non controlled document
EPCOS AG 2002. Reproduction, publication and dissemination of this data sheet, enclosures hereto and the information contained therein without EPCOS' prior express consent is prohibited. Purchase ord...