4-Line Filters
4-Line Filters for Installations and Systems
Power line filters for three-phase systems Rated voltage 440/250 V~, 50/60 ...
Description
4-Line Filters for Installations and Systems
Power line filters for three-phase systems Rated voltage 440/250 V~, 50/60 Hz Rated current 10 and 20 A Construction
s Four-line filter s Metal case
B84108
Features
s Medium insertion loss s Small size (similar to SIFI) s Easy to install
Applications
s Industrial electronics s Medical engineering s Elevators
Terminals
s Tab connectors 6,3 × 0,8 mm www.DataSheet4U.com
Marking Marking on component: Manufacturer’s logo, ordering code, rated voltage, rated current, date code Minimum marking on packaging: Manufacturer’s logo, ordering code Circuit diagram
LINE L1 L2 L3 N LOAD L1’ L2’ L3’ N’
SSB0334-1
292 03/01
4-Line Filters for Installations and Systems
Technical data Rated voltage V R Rated current IR Test voltage V P Leakage current l leak Climatic category Weight 440/250 V~, 50/60 Hz referred to 40 °C ambient temperature 1414 V–, 2 s (line/line) 2700 –, 2 s (lines/case) at 400 V~, 50 Hz
B84108
in accordance with EN 60068-1 25/085/21 (– 25 °C/+ 85 °C/21 days damp heat test) approx. 220 g
Characteristics and ordering codes IR A 10 20 l leak mA < 3,5 < 3,5 B84108-S1004-A110 B84108-S1004-A120 Ordering code Approvals
565-3
× —
× = approval granted
Dimensional drawing
84,5 15 14 74,5
50,8
31,5
4,7
63,5 89,5 Flachstecker Tab connector A6,3 × 0,8 A6,3 x 0,8 DIN 46244
DIN 46244
38+0,8
SSB0335-R
293 03/01
4-Line Filters for Installations and Systems
Insertion loss (typical values at Z = 50 Ω) unsymmetrical, adjacent bran...