(B84142-Bxx-R) Power line filters
2-Line Filters for Converters and Power Electronics
Power line filters for single-phase systems Rated voltage 250 V~, 50...
Description
2-Line Filters for Converters and Power Electronics
Power line filters for single-phase systems Rated voltage 250 V~, 50/60 Hz Rated current 8 A to 25 A Construction
s Two-line filter s Metal case
B84142-B*-R
Features
s Very high insertion loss
due to two-stage construction Low leakage current Easy to install Degree of protection: IP 201) Design complies with EN 133 200, UL 1283, CSA 22.2 No.8 1986 s Optimized for long motor cables and operation under full load
s s s s
Applications
www.DataSheet4U.com
s Frequency converters for motor drives, e.g.
– elevators – conveyor systems – pumps – traction systems – HVAC systems (heating, ventilation and air conditioning) s Power supplies Terminals
s Safe-to-touch terminal blocks
Marking Marking on component: Manufacturer’s logo, ordering code, rated voltage, rated current, rated temperature, date code Minimum marking on packaging: Manufacturer’s logo, ordering code
1) In accordance with IEC 60529: 1989; EN 60529: 1991; DIN VDE 0470-1
179 03/01
2-Line Filters for Converters and Power Electronics
Typical circuit diagram
B84142-B*-R
LINE L
LOAD L’
N
N’
SSB0772-K
Technical data Rated voltage V R Rated current IR Test voltage VP Overload capability Leakage current Ileak Climatic category 250 V~, 50/60 Hz Referred to 40 °C ambient temperature 1770 V–, 2 s (line/line) 2700 V–, 2 s (lines/case) 1,5 · IR for 3 min per hour or 2,5 · IR for 30 s per hour at 250 V~, 50 Hz 25/100/21 (– 25 °C/+ 100 °C/21 days damp heat test) in acco...