Document
3-Line Filters for Converters and Power Electronics
Power line filters for three-phase systems Rated voltage 440/250 V~, 50/60 Hz Rated current 8 A to 180 A Construction
s Three-line filter s Metal case
B84143-A*-R
Features
s s s s s s
High insertion loss Low leakage current Easy to install Degree of protection: IP 20 1) Space-saving design Design complies with EN 133200, UL 1283, CSA 22.2 No.8 1986 s Optimized for long motor cables and operation under full load s UL and CSA approval pending
www.DataSheet4U.com Applications
s Frequency converters for motor drives, e.g.
– elevators – pumps – traction systems – conveyor systems – HVAC systems (heating, ventilation and air conditioning) s Wind farms s Power supplies Terminals
s Safe-to-touch terminal blocks
Marking Marking on component: Manufacturer’s logo, ordering code, rated voltage, rated current, rated temperature, climatic category, date code Minimum marking on packaging: Manufacturer’s logo, ordering code
1) In accordance with IEC 60529:1989; EN 60529:1991; DIN VDE 0470-1
220 03/01
3-Line Filters for Converters and Power Electronics
Typical circuit diagram
B84143-A*-R
LINE L1
LOAD L1’
L2
L2’
L3
L3’
SSB0797-6
Technical data Rated voltage V R Rated current IR Test voltage V P Overload capability Leakage current I leak Climatic category 440/250 V~, 50/60 Hz Referred to 40 °C ambient temperature 1770 V–, 2 s (line/line) 2700 V–, 2 s (lines/case) 1,5 · IR for 3 min per hour or 2,5 · IR for 30 s per hour at 400 V~, 50 Hz 25/100/21 (– 25 °C/100 °C/21 days damp heat test) in accordance with EN 60068-1
221 03/01
3-Line Filters for Converters and Power Electronics
Characteristics and ordering codes IR A 8 12 16 25 36 50 80 120 150 180 Terminal cross section mm2 4 4 4 10 10 10 25 50 50 95 I leak mA R typ mΩ 40 20 15 8 3,8 2,0 1,0 0,75 0,4 0,4 Approx. weight kg 2,2 2,2 2,2 3,7 3,7 4,0 9,5 10 10 13
B84143-A*-R
Ordering code
< 3,5 < 3,5 < 3,5 < 3,5 < 3,5 <6 <6 <6 <6 <6
B84143-A8-R B84143-A12-R B84143-A16-R B84143-A25-R B84143-A36-R B84143-A50-R B84143-A80-R B84143-A120-R B84143-A150-R B84143-A180-R
For filters for higher currents see B84143-B*-S20, page 255. In comparison with the former series B84143-A*-S these filters are smaller, lower in weight and optimized in price.
222 03/01
3-Line Filters for Converters and Power Electronics
Dimensional drawings B84143-A8-R … B84143-A16-R
B84143-A*-R
20,5±0,5 36±1
81 max.
1,0±0,1
PE M6 x 25 163 max. 70±0,2
12,5±1 86 max.
L3 L2 L1 100±0,3
L3 L2 L1
Marking LINE LOAD
5,5±0,1 141 max.
Terminal blocks Anschlussklemmen 2 4 mm2
SSB1005-R
B84143-A25-R … A50-R
31±0,5
113 max.
46±1
91 max.
25±1
1±0,1
PE M6 x 25 216 max. 80±0,2
22,5±1 126 max.
L2 L1
LINE
LOAD
6,6±0,2 166 max.
PE L3
PE L3
Terminal blocks Anschlussklemmen 22 10 10 mm mm
156 max.
140±0,3
Marking
L2 L1
SSB0977-4
223 03/01
30±1
3-Line Filters for Converters and Power Electronics
B84143-A80-R
48,5±0,5
B84143-A*-R
90±1
141 max.
1,0±0,1
PE M10 x 35 300 max. 115±0,2
18±0,5 141 max.
PE
LINE
LOAD
PE
6,6±0,2 221 max.
Anschlussklemmen Terminal blocks 25 mm 25 mm22
155±0,3
Marking
171 max.
L1 L2 L3
L1 L2 L3
SSB0978-C
B84143-A120-R, B84143-A150-R
97±1
141 max.
54±0,5
62±0,8
1,0±0,1
PE M10 x 35 348 max. 115±0,2
18±0,5 141 max.
L1 L2 L3 PE
LINE
LOAD
6.6±0,2 261 max.
155±0,3
Marking
L1 L2 L3 PE
Anschlussklemmen Terminal blocks 2 50 mm 50 mm2
171 max.
SSB0979-K
224 03/01
65±0,8
3-Line Filters for Converters and Power Electronics
B84143-A180-R
B84143-A*-R
74±0,5
105±1
141 max.
1,2±0,1
PE M10 x 35 404 max. 301 max.
16±0,5 141 max.
L1 L2 L3 PE
Marking LINE LOAD
L1 L2 L3 PE
6,6±0,2 82,5±0,2 82,5±0,2
Terminal blocks Anschlussklemmen 22 95 mm mm
SSB0980-N
225 03/01
171 max.
155±0,3
62±0,8
3-Line Filters for Converters and Power Electronics
Insertion loss (typical values at Z = 50 Ω) unsymmetrical, adjacent branches terminated common mode, all branches in parallel (asymmetrical) differential mode (symmetrical) B84143-A8-R
100
SSB0798-E
B84143-A*-R
B84143-A12-R
100
SSB0799-M
αe
dB 80
αe
dB 80
60
60
40
40
20
20
0
10 4
10 5
10 6
10 7
Hz 10 8 f
0
10 4
10 5
10 6
10 7
Hz 10 8 f
B84143-A16-R
100
SSB0800-U
B84143-A25-R
100
SSB0801-3
αe
dB 80
αe
dB 80
60
60
40
40
20
20
0
10 4
10 5
10 6
10 7
Hz 10 8 f
0
10 4
10 5
10 6
10 7
Hz 10 8 f
226 03/01
3-Line Filters for Converters and Power Electronics
Insertion loss (typical values at Z = 50 Ω) unsymmetrical, adjacent branches terminated common mode, all branches in parallel (asymmetrical) differential mode (symmetrical) B84143-A36-R
100
SSB0802-B
B84143-A*-R
B84143-A50-R
100
SSB0985-U
αe
dB 80
αe
dB 80
60
60
40
40
20
20
0
0
10 4
10 5
10 6
10 7
Hz 10 8 f
10 4
10 5
10 6
10 7
Hz 10 8 f
B84143-A80-R
100
SSB0986-3
B84143-A120-R … B84143-A180-R
100
SSB0987-B
αe
dB 80
αe
dB 80
60
60
40
40
20
20
0
10 4
10 5
10 6
10 7
Hz 10 8 f
0
10 4
10 5
10 6
10 7
Hz 10 8 f
.