Smart Gas Sensor
p
| Sensors | OEM Sensor Applications
Smart Gas Sensor PYM 151 / PYM 152
Sensor Modules for Natural Gas Detection
Di...
Description
p
| Sensors | OEM Sensor Applications
Smart Gas Sensor PYM 151 / PYM 152
Sensor Modules for Natural Gas Detection
Dimensions in mm Patend pending
Meets EN 50 194 Requirements Unique NDiR Sensor Module Digital Output Factory-calibrated
New!
The Smart Gas Sensor is PerkinElmer’s response to OEM requirements for gas alarm sensors with long term stability. By use of the NDIR principle with a robust IR source and and a highly reliable pyroelectric detector, this sensor offers a digital alarm output, self monitor and diagnosis feature. It is supplied fully tested and calibrated for a minimum of 4 year long term operation. The PYM 151 provides one output with series signal transmission, whereas PYM 152 provides 4 discrete digital output signals.
Pre Alert Level Main Alert Level Response Time Warm-up Time
PYM 151/152
Unit
Remark
10%
LEL EN 50194
20%
LEL
max 30
sec EN 50194.
max 60
sec
Long Term Stability Operation Voltage Operation Current
max +/- 0,5% 6.,0
max 240mA
LEL/a V DC
Operation Temperature Environmental Humidity Storage Temperature
-10...+40 max 90%
-40...+70 -10...+50
°C rel Hum.
°C
non permanent permanent
Outputs provided:
PYM 151: Digital out :one wire, pre-alert, main alert, no-function, selfdiagnosis, with 4 pin plug PYM 152: 4 lines:pre-alert, main alert, nofunction, selfdiagnosis, with 7 pin plug.
Europe: PerkinElmer Optoelectronics GmbH & CoKG Wenzel Jaksch Str 31 65199 Wiesbaden / Germany Phone +49(0)611 492 0 Fax +49(0)611 492 170
N Am...