(MP1400 - MP1423) RTD Input Limit Alarm
INSTRUCTION MANUAL
RTD INPUT LIMIT ALARM
model MP1400 through MP1423
Thank you for choosing M-System. Before use, chec...
Description
INSTRUCTION MANUAL
RTD INPUT LIMIT ALARM
model MP1400 through MP1423
Thank you for choosing M-System. Before use, check specifications on the unit label. If you have any problems or questions with the product, please contact M-System’s Sales Office or representatives.
General Description
The M-PAC Model MP1400 through MP1423 accept 2- or 3-wire RTD inputs and provide relay contact closure(s) at a preset input level. The MP1400 Series reflects three styles of output selection:
MP1400 – MP1403 Single (Hi) trip, non-latching (DPDT, 3A) MP1410 – MP1413 Single (Hi) trip, latching (DPDT, 3A) MP1420 – MP1423 Dual (Hi/Lo) trip, non-latching (SPDT, 3A) Upscale burnout protection as standard Failsafe operation available
www.DataDInSedaihcdaebtaoenrtdL4EaUDdj.upcsrootavmbidleedfrom 1 to 100%
Installation [Scale: mm(inch)]
Operating temperature: -5 to +60°C (23 to 140°F) Operating humidity: 30 to 90% RH (non-condensing) Keep away from water, corrosive gas, dust and vibration. DIN rail mounting available for 11-pin-base modules. Use DIN rail of 35 mm width.
11-Pin Base
55 (2.17) min.
40 ± 0.2
40 ± 0.2 2–M4 SCREW
(1.57± .01) (1.57± .01)
Adjustments
Setpoint The MP1400 Series has five styles of setpoint adjustment: MP14X0 Top-accessed, 3-turn screw(s) MP14X2 Remote dial connection(s), 1k to 100k ohms MP14X3 DC-programmable, 0 to 1V The setpoint is adjustable over the entire input span.
A) Set deadband at its minimum (fully counterclockwise) before adjusting the setpoint.
B)...