industrial and commercial process and control systems
DINergy™ MD120 SERIES
Features Compact size, high efficiency and DIN Rail mounting 100-240VAC wide-range auto-select...
Description
DINergy™ MD120 SERIES
Features Compact size, high efficiency and DIN Rail mounting 100-240VAC wide-range auto-selection input Overcurrent, shortcircuit, and overvoltage protection DC OK LED Indicator w/remote indicator contact Adjustable DC output voltage Power boost for unusual start-up loading Parallel operation capable for power and redundancy Safety meets UL508, UL60950 and IEC60950 CE EN61000-3-2 compliant active PFC filtering EMI meets FCC15 B, EN55022 B and CISPR22 B High reliability, MTBF>200,000 hrs Operating temperature: -10°C to 70°C 3 year warranty UL 1604 Class 1 Division 2 compliant
Applications Micron DINergy™ units are suitable for industrial and commercial process and control systems, office facilities, telecom equipment, mechanical equipment, transport equipment, service and building automation, and electronic and electrical instrumentation. Specifications Model Input Voltage Input Current Frequency Inrush Current Earth Leakage Current Start-up Time PFC/Harmonics Rated Output Voltage/Current Output Pre-regulation (Set Point) Output Voltage Regulation Rated Output Current Min. Output Current Output Peak Current Efficiency Ripple & Noise Load Regulation 0.6A/240VAC, 1.3A/110VAC MD120-12-1 MD120-24-1 Rated 100-240VAC, 90-350VDC Range 85-264VAC MD120-48-1
0.7A/240VAC, 1.6A/110VAC 50-60Hz, ±6% Typ.<15A <3.5mA <1S >0.95/Meets EN61000-3-2
12VDC/8A 12.5±0.5% 10-16VDC 8-6A 0A 86%/230V
24VDC/5A 24.5±0.5% 22-28VDC 5-4.3A 0A 120% of rated...
Similar Datasheet