DIESEL ENGINE-GENERATOR SET
A tognum Group Brand
DIESEL ENGINE-GENERATOR SET 50-JC6DT3 50 ekW 60 Hz Standby
/ / 45 ekW / 60 Hz / Prime
208 - ...
Description
A tognum Group Brand
DIESEL ENGINE-GENERATOR SET 50-JC6DT3 50 ekW 60 Hz Standby
/ / 45 ekW / 60 Hz / Prime
208 - 600V
System Ratings
Standby
Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30% Voltage Dip Generator Model* Temp Rise Connection 240V** 1 1.0 60 50 50 208 135 362CSL1606 130°C/27°C
12 LEAD ZIG-ZAG
240V** 1 1.0 60 50 50 208 127 361CSL1613 130°C/27°C 4 LEAD
208V** 3 0.8 60 50 62.5 173 105 361CSL1601 130°C/27°C
12 LEAD LOW WYE
240V** 3 0.8 60 50 62.5 150 105 361CSL1601 130°C/27°C
12 LEAD HI DELTA
480V** 3 0.8 60 50 62.5 75 140 361CSL1601 130°C/27°C 12 LEAD HI WYE
600V** 3 0.8 60 50 62.5 60 138 361PSL1633 125°C/40°C 4 LEAD WYE
Prime
Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30% Voltage Dip Generator Model* www.DataSheet4U.com Temp Rise Connection 240V 1 1.0 60 45 45 188 91 362CSL1606 105°C/40°C
12 LEAD ZIG-ZAG
240V 1 1.0 60 45 45 188 115 361CSL1613 105°C/40°C 4 LEAD
208V 3 0.8 60 45 56.25 156 105 361CSL1601 105°C/40°C
12 LEAD LOW WYE
240V 3 0.8 60 45 56.25 135 105 361CSL1601 105°C/40°C
12 LEAD HI DELTA
480V 3 0.8 60 45 56.25 68 140 361CSL1601 105°C/40°C 12 LEAD HI WYE
600V 3 0.8 60 45 56.25 54 138 361PSL1633 105°C/40°C 4 LEAD WYE
* The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration. ** UL2200 Offered
2
// / /
50-JC6DT3
Facts
//...
Similar Datasheet