DIESEL ENGINE-GENERATOR SET
A tognum Group Brand
DIESEL ENGINE-GENERATOR SET 35-JC6DT3 35 ekW 60 Hz Standby
/ / 30 ekW / 60 Hz / Prime
208 - ...
Description
A tognum Group Brand
DIESEL ENGINE-GENERATOR SET 35-JC6DT3 35 ekW 60 Hz Standby
/ / 30 ekW / 60 Hz / Prime
208 - 600V
System Ratings
Standby
Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30% Voltage Dip Generator Model* Temp Rise Connection 240V** 1 1.0 60 35 35 146 52 361CSL1600 130°C/27°C
12 LEAD ZIG-ZAG
240V** 1 1.0 60 35 35 146 99 284CSL1550 130°C/27°C 4 LEAD
208V** 3 0.8 60 35 43.75 121 92 284CSL1508 130°C/27°C
12 LEAD LOW WYE
240V** 3 0.8 60 35 43.75 105 122 284CSL1508 130°C/27°C
12 LEAD HI DELTA
480V** 3 0.8 60 35 43.75 53 122 284CSL1508 130°C/27°C 12 LEAD HI WYE
600V** 3 0.8 60 35 43.75 42 123 284PSL1752 125°C/40°C 4 LEAD WYE
Prime
Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30% Voltage Dip Generator Model* www.DataSheet4U.com Temp Rise Connection 240V 1 1.0 60 30 30 125 66 361CSL1600 105°C/40°C
12 LEAD ZIG-ZAG
240V 1 1.0 60 30 30 125 102 284CSL1550 105°C/40°C 4 LEAD
208V 3 0.8 60 30 37.5 104 93 284CSL1508 105°C/40°C
12 LEAD LOW WYE
240V 3 0.8 60 30 37.5 90 93 284CSL1508 105°C/40°C
12 LEAD HI DELTA
480V 3 0.8 60 30 37.5 45 123 284CSL1508 105°C/40°C 12 LEAD HI WYE
600V 3 0.8 60 30 37.5 36 123 284PSL1752 105°C/40°C 4 LEAD WYE
* The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration. ** UL2200 Offered
2
// / /