DatasheetsPDF.com

3250-XC6DT2

MTU Onsite Energy

DIESEL ENGINE-GENERATOR SET

A tognum Group Brand DIESEL ENGINE-GENERATOR SET 3250-XC6DT2 3250 ekW  60 Hz  Standby /  /  2800 ekW / 60 Hz / Prime ...


MTU Onsite Energy

3250-XC6DT2

File Download Download 3250-XC6DT2 Datasheet


Description
A tognum Group Brand DIESEL ENGINE-GENERATOR SET 3250-XC6DT2 3250 ekW  60 Hz  Standby /  /  2800 ekW / 60 Hz / Prime 480 - 13.8kV System Ratings Standby Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30% Voltage Dip Generator Model* Temp Rise Connection 480V 3 0.8 60 3250 4062.5 4887 C/F C/F 130°C/27°C 6 LEAD WYE 600V 3 0.8 60 3250 4062.5 3909 C/F C/F 125°C/40°C 6 LEAD WYE 4160V 3 0.8 60 3250 4062.5 564 C/F C/F 130°C/27°C 6 LEAD WYE 12470V 3 0.8 60 3200 4000 185 C/F C/F 130°C/27°C 6 LEAD WYE 13200V 3 0.8 60 3200 4000 175 C/F C/F 130°C/27°C 6 LEAD WYE 13800V 3 0.8 60 3200 4000 167 C/F C/F 130°C/27°C 6 LEAD WYE Prime Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30% Voltage Dip Generator Model* www.DataSheet4U.com Temp Rise Connection 480V 3 0.8 60 2800 3500 4210 C/F C/F 105°C/40°C 6 LEAD WYE 600V** 3 0.8 60 2800 3500 3368 C/F C/F 105°C/40°C 6 LEAD WYE 4160V 3 0.8 60 2800 3500 486 C/F C/F 105°C/40°C 6 LEAD WYE 12470V 3 0.8 60 2750 3437.5 159 C/F C/F 105°C/40°C 6 LEAD WYE 13200V 3 0.8 60 2750 3437.5 150 C/F C/F 105°C/40°C 6 LEAD WYE 13800V 3 0.8 60 2750 3437.5 144 C/F C/F 105°C/40°C 6 LEAD WYE * The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration. ** UL2200 Offered 2 // /  / 3250-XC6DT2 Facts //  //  //  //  //  //  //  //  EPA Tier 2 ...




Similar Datasheet