Part Number 1250-XC6DT2
Manufacturer MTU Onsite Energy
Description DIESEL ENGINE-GENERATOR SET
Published Apr 1, 2011
Detailed Description A tognum Group Brand DIESEL ENGINE-GENERATOR SET 1250-XC6DT2 1250 ekW  60 Hz  Standby /  /  1125 ekW / 60 Hz / Prime ...
Datasheet PDF File 1250-XC6DT2 PDF File

1250-XC6DT2
1250-XC6DT2


Overview
A tognum Group Brand DIESEL ENGINE-GENERATOR SET 1250-XC6DT2 1250 ekW  60 Hz  Standby /  /  1125 ekW / 60 Hz / Prime 480 - 4160V System Ratings Standby Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30% Voltage Dip Generator Model* Temp Rise Connection 480V** 3 0.
8 60 1250 1562.
5 1879 3100 742RSL4048 130°C/27°C 4 BAR WYE 600V** 3 0.
8 60 1250 1562.
5 1504 4650 743RSS4288 125°C/40°C 4 BAR WYE 4160V 3 0.
8 60 1250 1562.
5 217 3100 742FSM4366 130°C/27°C 6 LEAD WYE Prime Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30% Voltage Dip Generator Model* com Temp Rise Connection 480V 3 0.
8 60 1125 1406.
25 1692 3100 742RSL40...