(T1K16TA / T1K08TA) Discrete AC Output Modules
Terminator I/O Specifications
AC OUTPUT MODULES
T1K-08TA T1K-16TA <---> <--->
Specifications
Outputs per Module Commons...
Description
Terminator I/O Specifications
AC OUTPUT MODULES
T1K-08TA T1K-16TA <---> <--->
Specifications
Outputs per Module Commons per Module Operating Voltage Range Output Voltage Range Max. Load Current ON Voltage Drop Max. Leakage Current Max. Inrush Current Min. Load OFF to ON Response ON to OFF Response Base Power Required Status Indicators Error Status Indications(LEDs ) Fuses (User Replaceable) T1K-FUSE-1 Weight
8 2 (4 pts. / common) isolated 17-240 VAC (47-63Hz) min./max. 15-264 VAC (47-63Hz) min./max. 1A / pt., 4A / common (subject to derating) 1.5VAC @ > 50mA, 4.0VAC @ < 50mA 4mA @ 264 VAC 10A for 10ms 10mA < 1ms < 1ms + 1/2 cycle 250mA @ 5VDC Logic side FU1 ON = fuse 1 blown FU2 ON = fuse 2 blown 2, (10A, 250V / common) 5 x 20 mm type 140g FU1/FU2 ON = fuse 1 or 2 blown FU3/FU4 ON = fuse 3 or 4 blown 4, (10A, 250V / common) 5 x 20 mm type 190g 450mA @ 5VDC
T1K-08TA
16
T1K-16TA
F IELD I/O
8-point and 16-point, AC output modules
The 8-point AC module uses a T1K-08B or T1K-08B-1 base, which is purchased separately. The 16-point AC module uses a T1K-16B or T1K-16B-1 base, which is purchased separately.
4 (4 pts. / common) isolated
Equivalent Output Circuit
w
w
w
.D
at aS
he
et 4U .c
w w w. a u to m at i o n d i re c t . c o m / f i e l d I O
om
Universal Field I/O
7–41
www.DataSheet4U.com
Terminator I/O Dimensions and Installation
DIMENSIONS AND INSTALLATION
It is important to understand the installation requirements for your Terminator I/O system. This will h...