Specification
Cells Per Unit Voltage Per Unit Capacity Weight Ma...
Powered by
www.datasheet4u.com
TPL 121250
12V 125Ah
Specification
Cells Per Unit
Voltage Per Unit Capacity Weight Maximum Discharge Current Internal Resistance Operating Temperature Range
TPL 121250 is a front terminal battery up to 12 years expected life under normal float charge As with all CSB batteries, all are rechargeable, highly efficient, leak proof and maintenance free.
6 12 125Ah @ 8hr-rate to 1.75V per cell @25 (77 ) Approx. 47kg(103.62 lbs) 800A(5sec) Approx. 4.1 m Discharge: -15 ~50 ( 5 ~122 ) Charge: -15 ~40 ( 5 ~104 ) Storage: -15 ~40 ( 5 ~104 ) Nominal Operating Temperature Range 25 3 (77 5 ) 2.275 0.025V / Cell at 25 (77 ) Temp. Float Charging
Voltage Coefficient 3.3mV/ ( 1.8mV/ ) Recommended Maximum Charging Current Limit 37.5A Equalization / Cycle Use Charging
Voltage 2.45V Temps coefficient 0.05mV/ ( 1.8mV/ )
Terminal
Terminal Hardware Initial Torque
Container Material
I2-Thread lead alloy recessed terminal to accept M6 bolt 105-in-lbs.(10.32 N-m) ABS(UL94-V0/File E88637)&(UL94-HB/File E50263)/ L.O.I higher than 28
CSB-manufactured VRLA batteries are ULrecognized components under UL924 and UL1989. CSB is also certified by ISO 9001 and ISO 14001.
Dimensions :
Unit: mm (inch)
Overall Height (H) 323±2.5 (12.7±0.1)
Length (L) 558.4±2.5 (22.0±0.1)
Width (W) 125.6±1.5 (4.9±0.06)
Constant Current Discharge Characteristics
F.V/Time 1.67V 1.70V 1.75V 1.80V 1.83V 1.85V 1.90V 15MIN 30MIN 60MIN 90MIN 232 147 86.3 63.0 220 142 84.4 61.8 199 132 81.2 59.3...