A tognum Group Brand
Diesel Engine-Generator Set 450-XS6DT3 450 ekW 60 Hz Standby
/ /
208 - 600V
System Ratings
...
A tognum Group Brand
Diesel Engine-Generator Set 450-XS6DT3 450 ekW 60 Hz Standby
/ /
208 - 600V
System Ratings
Standby
Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30%
Voltage Dip Generator Model Temp Rise Connection
** UL2200 Offered
208V** 3 0.8 60 450 562.5 1561 1285 572RSL4027 130°C/27°C 12 LEAD HI DELTA
240V** 3 0.8 60 450 562.5 1353 1285 572RSL4027 130°C/27°C 12 LEAD HI WYE
480V** 3 0.8 60 450 562.5 677 1085 572RSL4025 130°C/27°C 4 LEAD WYE
600V** 3 0.8 60 450 562.5 541 1037 572RSS4270 125°C/40°C 6 LEAD WYE
Facts
EPA Tier 3 Certified Engine-Generator Set Tested to ISO 8528-5 for Transient Response // UL2200, CSA Listing Offered // Accepts Rated Load in One Step Per NFPA 110, Level 1 // All engine-generator sets are prototype and factory tested // MTU Onsite Energy is a single source supplier // Global Product Support www.DataSheet4U.com // 2 Year Standard Warranty // Series 60 (6063HV35) Diesel Engine - 14.0 Liter Displacement - Electronic Unit Pump Injection - 4-Cycle
// // // //
//
//
Complete Range of Accessories Permanent Magnet Generator (PMG) - Brushless, Rotating Field - 300% Short Circuit Capability - 2/3 Pitch Windings Digital Control Panel(s) - UL Recognized, , NFPA 110 - Complete System Metering - LCD Display Cooling System - Integral Set-Mounted - Engine Driven Fan
2
// / /
450-XS6DT3
STANDARD EQUIPMENT
//
Engine
//
Digital Control ...