DIN RAIL-MOUNTABLE VOLTAGE SENSOR - imperix
Description
±800 V DIN RAIL-MOUNTABLE VOLTAGE SENSORS
GENERAL DESCRIPTION
The ModuLink ±800 V isolated voltage sensors are easyto-use devices, tailored for power electronics applications.
When employed with imperix’s BoomBox control platform, the sensors provide plug&play connectivity and can be directly powered by the control platform.
The devices produce a balanced full-differential output signal, proportional to the sensed voltage.
For best EMC performance, the output signal is typically meant to be carried by a shielded twisted pair embedded in RJ45-type cables.
Modulink sensors can be easily clipped on 35mm DIN rails and are compatible with up to 6 mm2 wires.
They guarantee the galvanic isolation of the sensing circuit up to 1 kVRMS
KEY FEATURES AND SPECIFICATIONS
–– ±800 V measuring range –– Minimum 60 kHz measurement bandwidth –– Balanced full-differential signal output –– Typical sensitivity of 2.
46 mV/V –– 1.
2 kVPK galvanic isolation (permanent) –– ±0.
15 % typical precision –– Compatible with standard ±15 V power supplies –– Mountable on 35 mm DIN rails
V+ 8x 1MΩ
0.
1%
2K7
0.
1%
V-
ISO5V
1
power supplies, 2
lters
3
3V3 4
VCC VCC GND
VO+
470pF
GND
5 VO-
6 GND 7 VEE 8 VEE
BOOMBOX CONFIGURATION
The recommended configuration for the BoomBox is shown in Table 1 :
Sensitivity 2.
46 mV/V
Filter
Gain
Filter = NONE G= 4
Input High-impedance
Table 1.
Suggested configuration of the BoomBox
Imperix recommends to consider calibrating each sensor for improved accuracy.
When difficult, at least the offset shall be compensated for.
6
5
4
3
2
1
MECHANICAL DIMENSIONS
D
D
38,5
-+
34,8 51,8
26,5
C
C
-+
94,5
ABSOLUTE MAXIMUM RATINGS
Parameter
Symbol Test conditions
B
Maximum tolerable differential input voltage
Vin,max,abs
Maximum working isolation voltage
VIORM
Highest allowable short-term isolation voltage (60s)
VIOTM
Power supply voltages
±VCC
Min.
Typ.
Max.
Unit
-
1.
6
-
kV
B
±12.
0
1.
2 4.
0 ±15.
0
±16.
0
kVPEAK kVPEAK V
SENSOR PAR...